概述
XGN2-12(Z)型鎧裝移開(kai)式交(jiao)流金屬封(feng)閉開(kai)關(guan)設備(以下簡稱開(kai)關(guan)柜)為額定(ding)電(dian)(dian)(dian)(dian)壓(ya)12kV,三相(xiang)交(jiao)流50Hz的戶內成套配(pei)電(dian)(dian)(dian)(dian)裝置,主要用于發(fa)電(dian)(dian)(dian)(dian)廠、工礦企業及高層建(jian)筑的配(pei)電(dian)(dian)(dian)(dian)以及電(dian)(dian)(dian)(dian)力(li)系統變電(dian)(dian)(dian)(dian)所的受電(dian)(dian)(dian)(dian)、送電(dian)(dian)(dian)(dian)及大型高壓(ya)電(dian)(dian)(dian)(dian)動(dong)機的起動(dong)等,并(bing)對電(dian)(dian)(dian)(dian)路(lu)實行控(kong)制、保護和(he)監測。
符合標(biao)準
l GB 3906 3.6~40.5kV交流金屬封閉開關(guan)設備和控制設備
l GB 1984 高壓交(jiao)流(liu)斷路器(qi)
l GB/T 11022 高壓開關(guan)設(she)(she)備和控制設(she)(she)備標準的共(gong)用技術要求
l GB/T 16927.1 高(gao)電壓試驗技術(shu)第一部(bu)分:一般試驗要求
使(shi)用環境條(tiao)件
l 海拔:不超過1000米(mi);
l 環境(jing)溫(wen)度(du)(du):最高(gao)溫(wen)度(du)(du)+40℃,最低(di)溫(wen)度(du)(du)-25℃,且(qie)日平均(jun)溫(wen)度(du)(du)不大(da)于+35℃;
l 相(xiang)對(dui)濕度(du):日平均(jun)相(xiang)對(dui)濕度(du)95%及以下(xia)(xia),月(yue)平均(jun)相(xiang)對(dui)濕度(du)90%及以下(xia)(xia);
l 抗震能力(li):地震烈度不超(chao)過8度;
l 安裝場所(suo):無(wu)火(huo)災、無(wu)爆炸危險、無(wu)嚴重污染、無(wu)化學腐蝕氣體及劇(ju)烈(lie)振動;
l 在超(chao)過(guo)GB 3906規定(ding)的正常環(huan)境條件(jian)下(xia)使用時,由用戶(hu)和制造廠協(xie)商。
主要技術(shu)參數
序號 | 項 目 | 單位 | 數 值 | ||
1 | 額定系統電壓 | kV | 10 | ||
2 | 額定電(dian)壓 | kV | 12 | ||
3 | 額定(ding)絕緣水平(ping) | 1min工頻 耐受(shou)電壓 | 隔離斷口 | kV | 48 |
相間及對地 | 42 | ||||
雷電沖(chong)擊耐受 電壓(峰(feng)值) | 隔離斷(duan)口(kou) | 85 | |||
相間及對地(di) | 75 | ||||
4 | 額定頻率 | Hz | 50 | ||
5 | 額(e)定電流 | A | 630、1250、1600、2000、2500、3150 | ||
6 | 額定短路開(kai)斷電流 | kA | 25、31.5、40 | ||
7 | 額定短(duan)時耐受(shou)電流4s | kA | 25、31.5、40 | ||
8 | 額(e)定(ding)峰值(zhi)耐受電流 | kA | 63、80、100 | ||
9 | 額定(ding)短(duan)路關合電流(liu)(峰值) | kA | 63、80、100 | ||
10 | 外形(xing)尺寸(寬×深×高) | mm | 1100(1200)×1200×2650 | ||
11 | 開關柜重量(liang) | kg | <1000 | ||
12 | 防護(hu)等級 | 外(wai)殼為IP3X |
訂(ding)貨(huo)須(xu)知
訂(ding)貨時請提供如下資料:
l 開(kai)關柜的(de)型號、數量、交貨日期及一次方案標(biao)號;
l 一(yi)次系統圖、二次原理圖和開(kai)關柜的排(pai)列圖;
l 主(zhu)母線額定電流和一次元件的型號、規格;
l 其它特(te)殊要求,與制造商(shang)(shang)協商(shang)(shang)。